IRC R310Bedroom needs an emergency escape opening
A basement sleeping room must have an egress window or door to the outside. Net clear opening 5.7 sq ft (5.0 if a grade-level opening), 24″ min height, 20″ min width, sill ≤ 44″ above the finished floor. A window well needs 9 sq ft of clear area and a ladder if deeper than 44″. Do not frame the north bedroom wall closed until this is resolved — cutting a well later means opening a finished wall.
IRC R314 / R315 · Village noteHardwired, interconnected smoke + CO
110-volt smoke alarms, series-wired and interconnected: one in the bedroom, one outside it, one on this level. Carbon monoxide within 15 ft of every sleeping room. Add them at rough-in, not as an afterthought.
Plainfield electrical amendmentBasement wiring is in conduit
Village rule: in basements, exposed extensions or additional outlets shall be in rigid conduit or EMT. NM (Romex) stapled to studs is the usual method elsewhere — not here. Budget EMT, connectors, and bends for every run. Flexible from basement to the floor above cannot exceed 18″.
NEC 210.8 · village amendmentGFCI within 6 ft of water and all basement receptacles
All basement convenience receptacles are GFCI. Dedicated single devices for sump, ejector, and furnace are excepted by village amendment. Bath: GFCI + an exhaust fan ducted outdoors.
IECC · Plainfield wall-section formBasement wall insulation — Zone 5A
R-15 continuous, or R-19 cavity, or R-13 cavity plus R-5 continuous. The 2×4 path that fits this house: 1″ XPS against the concrete (R-5) + R-13 kraft in the studs. Foil/kraft faces the warm (inside) side. The village form also allows cavity R-19 or continuous R-15.
IRC R317 / R602 · village worksheetTreated bottom plate, lapped top plates, 16″ OC
Every plate on the slab is pressure-treated, on sill sealer. Studs 16″ on center. Top plates lapped at corners and intersections. Headers: village addition worksheet calls 2-2×10 — use that on the perimeter; interior swing doors can be 2-2×6.
Village basement wall sectionDraftstop the top of the wall
½″ drywall (or approved equivalent) at the top plate against the joists. This is inspected. Fireblock foam at plumbing and electrical penetrations. Do not leave a chimney of open bays into the floor above.
IRC R403.1.6 practice · village 6′ OC noteAnchor the bottom plate
¼″ Tapcons or equivalent every 4 ft, two at each plate end, 2″ in from the end. Predrill. The village ½″ plate-bolt / 6′ OC note is for mudsills on new foundation — for furring, masonry screws at 4 ft are the field standard and will pass if they're in, tight, and not shot into the edge of the slab.
IRC R305Ceiling height
Habitable rooms 7′-0″ min. Beams and ducts can drop to 6′-4″ over a sliver of the room. Measure floor-to-joist in several spots and set stud length from the shortest. Slab isn't level.
Illinois Plumbing Code · IRC R303Bathroom
The rough-in already exists. Exhaust fan to exterior, GFCI, 20-amp bath circuit, tempered glass if a pane is in a tub wall. Moisture-resistant drywall (green/purple board or cement board) at the wet wall — later, not this week.
IFGC · IMCDon't box in the furnace
The furnace and water heater stay in storage. They need combustion air and 30″ of service clearance. A louvered door or a transfer grille high and low. If you starve the furnace you'll fail final and, worse, you'll make CO. Do not build a separate mechanical room.
Village of Plainfield Building DepartmentPermit before you snap a line
A basement finish is a permit job: plans, wall section, and the inspection list. Cut-off for scheduling is 3:00 p.m. the day before. Cancel after 8:30 a.m. the day-of and you pay a reinspect. Phone (815) 439-2937. 14400 S. Coil Plus Drive.